It's a lot. But here are my most recent notes.
Note that the pipe & lock locations different by distro, as does the nut username. So these files won't drop in and work anywhere.
The dummy driver will need to be installed and configured.
Mine also have several layers of timers on battery an online:
- NUT server: In ONBATT I use sleep commands to time subsequent commands. These will always run.
- NUT server: Onbatt5 is a upssched timer I set to 300s and is cancelled if the UPS returns to line power.
- NUT client: Onbatt30s starts on the client when it gets an ONBATT status from the server.
Most configs would have the client side cancel their timers if power returns. In my case I don't want that because I prefer more certainty of state so that I know it's safe to power cycle an outlet to bring a device back up. My NUT server runs on an old pi 3b with a read-only file system. So it never needs a safe shutdown. It's the last man standing to bring everything else back up if the UPS returns to line power before the battery is exhausted. That's why there is no local shutdown on the NUT server config.
Each snmpset... is a truncated version of an outlet power command.
Also, the wall commands were a debug aid. Uncomment to use, but test a command first. Wall doesn't work on some distros.
NUT Server
NUT.CONF:
MODE=netserver
UPS.CONF:
[ups]
desc = My UPS
driver = dummy-ups
port = /opt/ups/ups.seq
UPSD.CONF:
LISTEN 0.0.0.0 3493
## all interfaces
## STATEPATH /var/run/nut
UPSD.USERS:
[upsuser]
password = <pw>
actions = set
upsmon master
[upssrv]
password = <pw>
actions = set
upsmon slave
[upspi]
password = <pw>
actions = set
upsmon slave
UPSMON.CONF:
RUN_AS_USER nut
#RUN_AS_USER root
MONITOR ups@localhost 1 upsuser <pw> master
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established"
NOTIFYMSG COMMBAD "Communications with UPS %s lost"
NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
NOTIFYMSG NOCOMM "UPS %s is unavailable"
NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
NOTIFYFLAG ONLINE WALL+EXEC+SYSLOG
NOTIFYFLAG ONBATT WALL+EXEC+SYSLOG
NOTIFYFLAG LOWBATT SYSLOG+WALL
NOTIFYFLAG FSD SYSLOG+WALL
NOTIFYFLAG COMMOK SYSLOG+WALL
NOTIFYFLAG COMMBAD SYSLOG+WALL
NOTIFYFLAG SHUTDOWN SYSLOG+WALL
NOTIFYFLAG REPLBATT SYSLOG+WALL
NOTIFYFLAG NOCOMM SYSLOG+WALL
NOTIFYFLAG NOPARENT SYSLOG+WALL
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -P +0"
NOTIFYCMD "/usr/sbin/upssched"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
# POWERDOWNFLAG /var/run/killpower
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
CERTVERIFY 0
FORCESSL 0
UPSSCHED.CONF:
CMDSCRIPT /etc/nut/upssched-cmd
PIPEFN /var/run/nut/upssched.pipe
LOCKFN /var/run/nut/upssched.lock
AT ONBATT ups@localhost CANCEL-TIMER online3
AT ONBATT ups@localhost CANCEL-TIMER online10
AT ONBATT ups@localhost START-TIMER onbatt5 300
AT ONBATT ups@localhost EXECUTE onbattnotify
AT ONLINE ups@localhost CANCEL-TIMER onbatt5
AT ONLINE ups@localhost START-TIMER online3 180
AT ONLINE ups@localhost START-TIMER online10 600
AT ONLINE ups@localhost EXECUTE onlinenotify
UPSSCHED-CMD
#! /bin/bash
#
# This script should be called by upssched via the CMDSCRIPT directive
# The first argument passed to your CMDSCRIPT is the name of the timer
# from your AT lines.
logger -t upssched-cmd "Calling upssched-cmd $1"
wall "Calling upssched-cmd $1"
UPS="ups@localhost"
HOST=$( uname -n)
TIMESTAMP=$(date +%Y%m%d%H%M%S)
STATUS=$( upsc $UPS ups.status )
CHARGE=$( upsc $UPS battery.charge )
CHMSG="UPS[STATUS]:$CHARGE%"
case $1 in
onbattnotify)
# srv and pi are upsmon clients and will shut down on their own after a 30s delay.
# Log the Notification.
logger -t upssched-cmd "UPS on Battery Power. Servers will shutdown in 30 seconds. Switch shutdown in 5 minutes. $CHMSG $TIMESTAMP"
wall "upssched-cmd onbattnotify: UPS on Battery Power. Servers will shutdown in 30 seconds. Switch shutdown in 5 minutes. $CHMSG"
# wall "upssched-cmd: sleeping to give servers time to poweroff"
sleep 120s
# Power off PDU outlets to save power.
logger -t upssched-cmd "UPS on Battery Power. PDU outlets 4-srv-drives, 5-srv, 7-pi and 8-homeassistant power down NOW. $CHMSG $TIMESTAMP"
snmpset ...
snmpset ...
snmpset ...
snmpset ...
# wall "End upssched-cmd $1"
;;
onbatt5)
# Shut down servers
logger -t upssched-cmd "UPS on Battery Power. PDU outlets 3-switch and 8-homeassistant power down NOW. $CHMSG $TIMESTAMP"
snmpset ...
snmpset ...
# wall "End upssched-cmd $1"
;;
onlinenotify)
# Log the notification.
logger -t upssched-cmd "UPS back on Line Power. Bringing up network in 3 minutes, servers in 10 minutes. $CHMSG $TIMESTAMP"
# wall "End upssched-cmd $1"
;;
online3)
# Power on PDU outlets for main switch to prep for server startup.
logger -t upssched-cmd "UPS back on Line Power. Bringing up PDU outlet 3-switch NOW. $CHMSG $TIMESTAMP"
snmpset ...
# wall "End upssched-cmd $1"
;;
online10)
# Power on PDU outlets for servers now.
logger -t upssched-cmd "UPS on Line Power. Bringing up PDU outlets 5-srv, 7-pi, 8-homeassistant NOW. $CHMSG $TIMESTAMP"
snmpset ...
snmpset ...
snmpset ...
# wall "End upssched-cmd $1"
;;
upsgone)
logger -t upssched-cmd "UPS communication has been gone awhile on $HOST. $TIMESTAMP"
;;
)
logger -t upssched-cmd "Unrecognized command: $1"
;;
esac
NUT Client
NUT.CONF
MODE=netclient
UPS.CONF
maxretry = 3
UPSD.CONF
# empty
UPSD.USERS
# empty
UPSMON.CONF
RUN_AS_USER nut
MONITOR ups@192.168.0.77 1 upspi <pw> slave
NOTIFYCMD /usr/sbin/upssched
SHUTDOWNCMD "sudo /sbin/shutdown -P +0"
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established"
NOTIFYMSG COMMBAD "Communications with UPS %s lost"
NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
NOTIFYMSG NOCOMM "UPS %s is unavailable"
NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
NOTIFYFLAG ONLINE WALL+EXEC+SYSLOG
#+SYSLOG+WALL
NOTIFYFLAG ONBATT WALL+EXEC+SYSLOG
#+SYSLOG+WALL
NOTIFYFLAG LOWBATT SYSLOG+WALL
NOTIFYFLAG FSD SYSLOG+WALL
NOTIFYFLAG COMMOK SYSLOG+WALL
NOTIFYFLAG COMMBAD SYSLOG+WALL
NOTIFYFLAG SHUTDOWN SYSLOG+WALL
NOTIFYFLAG REPLBATT SYSLOG+WALL
NOTIFYFLAG NOCOMM SYSLOG+WALL
NOTIFYFLAG NOPARENT SYSLOG+WALL
MINSUPPLIES 1
POLLFREQ 10
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
UPSSCHED.CONF
CMDSCRIPT /etc/nut/upssched-cmd
PIPEFN /run/nut/upssched.pipe
LOCKFN /run/nut/upssched.lock
AT ONBATT ups@192.168.0.77 EXECUTE onbattnotify
AT ONBATT ups@192.168.0.77 START-TIMER onbatt30s 30
# Disabled the online cancel actions in favor of having certainty on the state.
# Servers will go down on an OB event, but that's fine. When Nutpi sees it back
# OL it will bring up the servers
#AT ONLINE ups@192.168.0.77 CANCEL-TIMER onbatt30s
#AT ONLINE ups@192.168.0.77 EXECUTE onlinenotify
UPSSCHED-CMD
#! /bin/sh
#
# This script should be called by upssched via the CMDSCRIPT directive.
#
# The first argument passed to your CMDSCRIPT is the name of the timer
# from your AT lines.
logger -i -t upssched-cmd "Calling upssched-cmd $1"
UPS="ups@192.168.0.77"
HOST=$( uname -n)
STATUS=$( upsc $UPS ups.status 2>&1 | grep -v '^Init SSL' )
CHARGE=$( upsc $UPS battery.charge 2>&1 | grep -v '^Init SSL' )
CHMSG="$UPS[$STATUS]:$CHARGE%"
case $1 in
onbattnotify)
# Log the Notification.
logger -t upssched-cmd "UPS on Battery Power. Shutting down $HOST in 30 seconds. $CHMSG"
wall "upssched-cmd: UPS on Battery Power. Shutting down $HOST in 30 seconds. $CHMSG"
;;
onbatt30s)
# Shut down servers
logger -t upssched-cmd "UPS on Battery Power. $HOST shutting down NOW. $CHMSG"
wall "upssched-cmd: UPS on Battery Power. $HOST shutting down NOW. $CHMSG"
sudo shutdown -P +0
;;
# onlinenotify)
# # Log the notification.
# logger -t upssched-cmd "UPS back on Line Power. $HOST is already online. $CHMSG"
# wall "upssched-cmd: UPS back on Line Power. $HOST is already online. $CHMSG"
# ;;
upsgone)
logger -t upssched-cmd "UPS communication has been gone awhile on $HOST."
;;
*)
logger -t upssched-cmd "Unrecognized command: $1"
;;
esac