Microwave has been on the counter for a few weeks, since neutral on this one kept floating.

Microwave is now back in its cubby, and we have a big increase in counter space.

you are viewing a single comment's thread
view the rest of the comments
[–] [S] 3 points 20 hours ago (6 children)

This is a sufficient distance from the sink to not need one.

We have a bunch of others that will have to swapped for GFCI, eventually. Just not today.

  • source
  • parent
  • hideshow 6 child comments
  • [–] 10 points 20 hours ago* (1 child)

    You only really need one, the first outlet in series should be GFCI and then there is a "load" side and anything connected to that is also protected. If you aren't sure, you can get a tester to trigger a GFCI fault and if it is connected to one, it will trip.

  • source
  • parent
  • hideshow 1 child comment
  • [–] 4 points 16 hours ago* (last edited 13 hours ago)

    We found out on accident that we had one of these. Had an outlet that didn't work, fuse box wasn't tripped. Eventually, found one of those outlet buttons on a hidden outlet that was tripped. That was an annoyance.

  • source
  • parent
  • [–] 7 points 20 hours ago (3 children)

    You may want to check what year nec your state has adopted. It unfortunately is required now. Also 20A is required unless you have three or more outlets on the circuit (a duplex counts as two).

  • source
  • parent
  • hideshow 3 child comments
  • [–] 11 points 20 hours ago (1 child)

    These usually only apply to new construction. Assuming it was built to code initially, you can replace parts to that same standard forever. You can't just connect a 15 amp wire (usually 14-gauge) to a 20a outlet/breaker - that would be a horrible violation of all codes. But you can replace that existing 15a outlet as needed.

    You don't have to run a 20a circuit unless you're running a new line.

  • source
  • parent
  • hideshow 1 child comment
  • [–] [S] 2 points 14 hours ago

    Yeah, I know what my province's code says and I followed it.

    Also, 20A??! Unless there are three OR MORE outlets??! I don't know where that would be code. I don't think I want to know.

  • source
  • parent