[–] 2 points 1 week ago (1 child)

And that would all count as "not using it correctly".

As I said, they are many ways to very easily use it incorrectly. Being overconfident about it is one, which is why I have an inlet and an interlock.

  • source
  • parent
  • hideshow 2 child comments
  • There are zero ways to use this cord correctly. Do not tell people otherwise. The proper generator connection is to, as you just said, use a proper generator inlet and interlock like you said you use. Anyone using a cord like this is using it incorrectly as there is no correct way to use it. Both the CEC and the NEC expressly forbid these. All it takes is for a child to unplug the wrong end and touch the exposed prongs and they will get shocked.

    A proper generator inlet should have the male ends in a recessed inlet box connected to either a transfer switch or an interlocked generator panel.

  • source